General
Operating Temperature
Storage Temperature
Operating Humidity
Mechanical Vibrations
Operating Altitude
Regulatory Standards
Safety
Emission
Immunity
-40 ºC to +70 ºC (-40 ºF to 158 ºF)
Notes: 1) When using a metal housing option, the maximum operating
temperature outside the housing is +60 ºC (140 ºF).
2) ACT module and Motorola radios operating temperature range is:
-30 ºC to +60 ºC (-22 ºF to 140 ºF).
The full operating temperature range is supported when using redundant
12V power supplies. When using dual AC power supply or dual 18-72 V
DC power supply, the maximum ambient operating temperature of the RTU
is limited to:
• 50°C (122°F) - when installed inside a metal chassis or closed
cabinet.
• 60°C (140°F) - when installed without enclosure or closed cabinet.
-55 ºC to +85 ºC (-67 ºF to 185 ºF)
5% to 95% RH @ 50 ºC without condensation
Per EIA / TIA 603 Base-station, Sinusoidal 0.07mm @ 10 to 30 Hz, 0.0035
mm @ 30-60 Hz
-400m to +4000 meter (-1312 ft to + 13120 ft) above sea level
Note: When using 18-72V DC or 100-240 VAC Power supply the operating
altitude is -400 to +3000m
UL 60950-1 (UL listed), CSA 22.2-950-1, EN60950-1, IEC 60950-1,
AS/NZS 60950
FM/cFM certified as Nonincendive Class I, Division 2 - standard FM 3611
(Note: FM approval refers to model F7509 only and most of the ACE3600
options.)
Emission standards for industrial environments
CFR 47 FCC part 15, subpart B (class A);
CE EMC: EN50081-2/EN61000-6-4
(CISPER 11 / EN55011 class A)
Immunity standards for industrial environments
Per EN50082-2 /IEC 61000-6-2
A-3