Event 1 is the same as that of Event 2 (see Fig. 46: d2,
d5, d8 and d10).
The sys tem will not gen er ate the Cus tom ized
event, if the sta tus of Event 1 is dif fer ent from that
of Event 2, when the Win dow is not run ning (see
Fig. 46: b3, b6 and b9).
Event 1 and Event 2 Spot, NO Win dow (NOT
ALLOWED)
If you ap ply the XOR Op er a tor to two Spot Events,
you MUST pro gram the Win dow.
Event 1 and Event 2 Spot, WITH Win dow
When cal cu lat ing the XOR re sult of two Spot Events,
you must con sider them as both end ing when the Win -
dow ex pires. In this way, the Cus tom ized Event will start
when the sta tus of Event 1 is dif fer ent from that of
Event 2 (see Fig. 46: e1, e3 and e5).
The Cus tom ized Event will end when the sta tus of
a)
Event 1
Event 2
XOR
b)
Event 1
Event 2
Window
XOR
c)
Event 1
Event 2
XOR
d)
Event 1
Event 2
Window
XOR
e)
Event 1
Event 2
Window
XOR
Fi gu re 46 The XOR Op er a tor mode
KYO320
Event 1 is the same as that of Event 2 (see Fig. 46: e2,
e4, and e6).

Scheduler - Arming

You can pro gram the Sched uler to man age up to 16
Day Models (e.g. Week day, Hol i days, etc.), each with
up to 4 Arm and 4 Dis arm op er a tions per Par ti tion.
!
You can pro gram the au to matic Arm/Dis arm pa ram e -
ters in the Arming page.
To cre ate the Day Models — click the Models tab.
Partitions This field shows the Par ti tion De scrip tions
(to be pro grammed in the Par ti tions page).
1st Dis. / 2nd Dis. / 3rd Dis. / 4th Dis. These fields will
al low you to set up to 4 Dis arm times for the cor re spond ing
Par ti tion.
PRO GRAM MING FROM THE PC
The Sched uler Ac tions will be ig nored dur ing
the pro gram ming ses sion.