Power Supply - AEMC 5050 User Manual

Megohmmeter
Hide thumbs Also See for 5050:
Table of Contents

Advertisement

Capacitance Measurement (after discharge of tested component):
Range
0.005 to 9.999µF
10.00 to 49.99µF
Leakage Current Measurement:
Range
0.000 to 0.250nA
0.251 to 9.999nA
10.00 to 99.99nA
100.0 to 999.9nA
1.000 to 9.999µA
10.00 to 99.99µA
100.0 to 999.9µA
1000 to 3000µA
Calculation of Terms DAR and PI:
Range
0.02 to 50.00
Calculation of Term DD:
Range
0.02 to 50.00
7.4

POWER SUPPLY

■ Rechargeable battery NiMh (8 x 1.2V / 3.5Ah).
■ Recharge: 85 to 256V / 50-60Hz.
Minimum Battery Charge Life (per NF EN 61557-2):
Test Voltage
500V
1000V
2500V
5000V
Megohmmeter Models 5050 & 5060
Resolution
Resolution
Resolution
Resolution
Nominal Charge
500kΩ
1MΩ
2.5MΩ
5MΩ
1nF
10nF
15% of Reading ± 10cts
1pA
10pA
100pA
1nA
10nA
100nA
1µA
0.01
0.01
Number of Measurements
5s on nominal charge (with 25s
pause between each measurement)
Accuracy
10% of Reading ± 1ct
Accuracy
10% of Reading
5% of Reading
10% of Reading
Accuracy
5% of Reading ± 1ct
Accuracy
10% of Reading ± 1ct
6500
5500
4000
1500
43