6.3.6 Bandwidth

Range of influence: 100 Hz to 5 kHz (harmonics)
Presence of the fundamental at 50/60 Hz (THD = 50 %)
V1, V2: 0.5 % @ 2.1 kHz / -3 dB @ 5 kHz
I1, I2 (direct input): 0.5 % @ 1.75 kHz / -3 dB @ 5 kHz
P1, P2: 0.5 % @ 1.25 kHz / -3 dB

6.3.7 Disturbed Signals

The following signal bandwidth is 6 kHz, 5 % I
Signal type
Phase cut-off
Bridge rectifiers have a waveform that is not supported by the PEL 52.

6.4 POWER SUPPLY

Power supply (between terminals V1 and N)
Operating range: (100 to 600) V
DC voltage of 100 V or more will prevent the operation of the power supply.
ƒ
Power: (3 to 5) W depending on input voltage.
Current:
at 100 Vac, 100 mApeak and 17 mA
ƒ
at 600 Vac, 500 mApeak and 0.026 mA
ƒ
Battery
(2) NiMH rechargeable elements type AAA 750 mA·h
Lifespan: at least 500 charge / discharge cycles or 2 years
ƒ
Charging time: approx. 5 h
ƒ
Charging temperature: (50 to 104) °F (10 to 40) °C
ƒ
Battery life with active Wi-Fi: 1 hr min, 3 h typical
ƒ
NOTE: When power is off, the real-time clock is retained for more than
20 days.
Power & Energy Logger Model PEL 52 - User Manual
dimmer
MiniFlex
Square
MiniFlex
< I ≤ 50 % I
nom
Sensor
MN193 clamp
MA194
®
MN193 clamp
MA194
®
Table 15
: Inrush current: 1.9 Apeak
RMS
RMS:
.
nom
Typical influence
< 1 %
< 3 %
< 1 %
< 3 %
Inrush current: 5.3 Apeak
57