Chapter 18. Configurable Parameter Reference Guide
To avoid confusion between letter O and number 0, Ø represents number zero or logic null.
Parameter Name
Alarm 1 Enable
Alarm 1 Function
Alarm 1 Level
Alarm 1 Trigger
Alarm 2 Enable
Alarm 2 Function
Alarm 2 Level
Alarm 2 Trigger
Alarm 3 Enable
Alarm 3 Function
Alarm 3 Level
Alarm 3 Trigger
Alarm Hysteresis
Alarm Latch
MAN0984_Iss 3_02/16
Pt. No. 3011M5001_3
Configurable Parameter Reference Guide
Parameter Description
Alarm enable/disable.
Ø = Disabled 1 = Enabled
Type of alarm function. Default is threshold. Ø=Threshold, 1=STEL,
2=TWA
Alarm 1 threshold concentration
Alarm trigger option. Ø = Rising 1 = Falling
Alarm enable/disable. Ø = Disabled 1 = Enabled
Type of alarm function. Default is threshold. Ø=Threshold, 1=STEL,
2=TWA
Alarm 2 threshold concentration
Alarm trigger option. Ø = Rising 1 = Falling
Alarm enable/disable. Ø = Disabled 1 = Enabled
Type of alarm function. Default is threshold. Ø=Threshold, 1=STEL,
2=TWA
Alarm 3 threshold concentration
Alarm trigger option. Ø = Rising 1 = Falling
Alarm hysteresis is to avoid the alarm from frequent on/off when the gas
reading is close to the alarm threshold. When clearing the gas alarm,
the gas reading should go below gas alarm threshold hysteresis.
The hysteresis is defined in % of Full range (Default 2 %FSD)
Alarm latch option. Alarm will be continued until manual user reset if
latching is enabled.
Ø: Disabled, 1: Enabled
Applies to
Read/Write
All
All
All
All
All
All
All
All
All
All
All
All
All
All
135
Default
Measurement
Value
units
R/W
1
n/a
R/W
Ø
n/a
R/W
20 %FSD
conc.
1 for O
, Ø for
2
R/W
n/a
other gases
R/W
1
n/a
R/W
Ø
n/a
R/W
40 %FSD
conc.
1 for O
, Ø for
2
R/W
n/a
other gases
R/W
1
n/a
R/W
Ø
n/a
R/W
60 %FSD
conc.
R/W
Ø
n/a
R/W
2
%FSD
R/W
1
n/a
Technical Handbook