UNIPOINT OPERATING MANUAL

5 Default Configuration

Unipoint has user configurable settings that allow the set up of the system to individual
application requirements. Unipoint is supplied from the factory with a default configuration.
These configurations are based on settings typically used in gas detection systems.
Details of how to reconfigure Unipoint are given in section 7.

5.1 Unipoint mV Input Version

Function
Password
Display range and units
Alarm Relay 1
Alarm Relay 2
Alarm Relay 3
Fault Relay
Inhibit

5.2 Unipoint 4-20mA Input Version

Function
Password
Display range and units
Current input
Alarm Relay 1
Alarm Relay 2
Alarm Relay 3
Fault Relay
Inhibit
Detector Type
Default configuration
000 (Disabled)
0-100%LEL
Alarm level 1 10%LEL (Rising)
Non-latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm level 2 25%LEL (Rising)
Non-latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm level 3 50%LEL (Rising)
Latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Non-latching, normally energized, de-energizes on fault.
(Single Pole change over, 240Vac/30Vdc, 3A max)
Controller inhibit activates fault relay.
Default configuration
000 (Disabled)
0-100ppm
0 mA
Fault (open circuit)
4.0 to 20.0mA
Gas reading (normal operation)
1.5 to 2.5mA
Inhibit from sensor (configuration mode)
>20.0mA
Overrange
Alarm level 1 10% of full scale (Rising)
Non-latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm level 2 25% of full scale (Rising)
Non-latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm level 3 50%LEL (Rising)
Latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Non-latching, normally energized, de-energizes on fault.
(Single Pole change over, 240Vac/30Vdc, 3A max)
Controller inhibit activates fault relay and de-activates alarm relays.
Field inhibit active (1.5 to 2.5mA on detector input).
2 Wire 4-20mA
10
2306M5001 MAN0638 ISSUE 7 01/2011