5.7.4.2

Series commissioning with STARTER

Upload a parameter set with STARTER
Prerequisites
● An inverter with an apropriate parameter set is available (upload inverter)
● STARTER is installed on the PC used for series commissioning
● Supply voltage is active for the upload inverter
● The upload inverter is in "Ready State".
Connect the STARTER PC via the Option Port (USS on RS232, peer to peer) to the upload
inverter (PC connection Kit requiered), press the online button
activating the button
Note
Upload with STARTER to MMC
If you want to upload a parameter set with STARTER to an MMC, P0010, P0802 must be set
via the expert list.
Download a parameter set with STARTER
Prerequisites
● Supply voltage is active for the download inverter
● The download inverter is in "Ready State".
Connect the STARTER PC via the Option Port (USS on RS232, peer to peer) to the
download inverter (PC connection Kit requiered), press the online button
download by activating the button
Note
If you want to perform an manual download of a parameter set with STARTER from an
MMC, P0010, P0803 and P0804 must be set via the expert list.
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
.
. The data set must be saved in the EEPROM.
Commissioning (software)
5.7 Commissioning modes
and perform the upload by
and perform the
5-49