Commissioning (software)
5.7 Commissioning modes
Manual Download of a parameter set with an MMC
Note
The following important restrictions should be considered when using the download
procedure:
• During the download the inverter will not react to any commands.
• Once the download procedure has started, it cannot be interrupted.
• After upload and download of parameters between differing Control Units, parameter
• Parameter download from a different CU might fail with F0063 if parameters cannot be
• If the download fails, the inverter reverts to the previous parameters from the EEPROM.
Prerequisites
● Supply voltage is active for the download inverter
● The download inverter is in "Ready State".
Parameter
Description (Parameter name and factory setting (if not variable) in bold)
Insert the MMC to the download inverter and perform the manual download according the flow
chart.
P0010 = 30
Commissioning parameter*
0: Ready
1: Quick commissioning
2: Inverter
30: Factory setting, parameter transfer
95: Safety commissioning (for CUs with fail-safe functions only)
P0804 = ?
Select Clone file (for download)
0: clone00.bin
...
99: clone99.bin
P0803 = 2
Transfer data to EEPROM
0: Disabled
1: Start OP Transfer
2: Start MMC Transfer
If the download has been completed successfully, P0010 and P0803 will be set to 0 and the
"RDY" LED is on.
If the upload has failed, F0061 (MMC-PS not fitted) or F0062 (MMC-PS contents invalid) resp.
F0063 (MMC-PS contents incompatible) will be displayed, LED "SF" (red) is on.
In this case insert a proper MMC and attempt another download or perform a factory reset.
After a successful manually download remove the MMC from inverter and insert it to the next
download inverter. Then perform the download steps again until the series commissioning has
been completed for all inverters.
5-54
settings must be checked.
downloaded (Check P949 for the (first) parameter number which cannot be downloaded).