Commissioning (software)
5.8 Commissioning the Fail-safe Functions
Filter time of fail-safe digital inputs
Parameter
Description
P9651 = ?
Safe input filter delay time
Defines the response time delay of the safe digital inputs. Signals that
are shorter than the specified time are not processed as fail-safe
signals but ignored. Any noise shorter than the parameterised filter
time will not trigger a fail safe function at the related fail safe digital
input.
P9851 = ?
Safe input filter delay time
Refer to P9650.
5-70
Unit
Default
ms
5
s
0.005
Operating Instructions, 11/2006, A5E00766042B AA
Min.
Max.
0
1000
0.000
1.000
Control Units CU240S