Commissioning (software)
5.7 Commissioning modes
Assigning digital output functions
Parameter
Description (Parameter name and factory setting (if not variable) in bold)
P0731 = 52:3
BI: function of digital output 0 (DO0), defines the source for digital output 0
Terminal 18: DO0, NC/Terminal 19: DO0, NO/Terminal 20: DO0, COM
52:3 Inverter fault active
P0732 = 52:7
BI: function of digital output 1,defines the source for digital output 1
Terminal 21: DO1, NO/Terminal 22: DO1, COM
52:7 Inverter warning active
P0733 = 0:0
BI: function of digital output 2, defines the source for digital output 2
Terminal 23: DO0, NC/Terminal 24: DO0, NO/Terminal 25: DO0, COM
0:0 Digital output disabled
P0748
Invert digital outputs
Bits 0, 1 and 2 can be used to invert the signals of digital outputs 0, 1 and 2
Frequency setpoint set
Parameter
Description (Parameter name and factory setting (if not variable) in bold)
P1000 = ?
Selection of frequency setpoint
0: No main setpoint
1: MOP setpoint (P1031 ... P1040)
2: Analog setpoint (P0756 ... P0762), factory setting for CU240S
3: Fixed frequency (P1001 ... P1023)
6: Fieldbus (P2050 ... P02091), factory setting for CU240S DP and CU240S DP-F, not
available with CU240S)
7: Analog setpoint 2
10: Additional setpoint (1 = MOP) + Main setpoint (0 = No main setpoint)
11: Additional setpoint (1 = MOP) + Main setpoint (1 = MOP)
12: Additional setpoint (1 = MOP) + Main setpoint (2 = Analog setpoint)
...
62: Additional setpoint (6 = Fieldbus) + Main setpoint (2 = Analog setpoint)
63: Additional setpoint (6 = Fieldbus) + Main setpoint (3 = Fixed frequency)
...
Frequency setpoint via MOP (P1000 = 1)
Parameter
Description (Parameter name and factory setting (if not variable) in bold)
P1031 = 0
Setpoint memory of the MOP
The last motorized potentiomenter setpoint, which was active before the OFF command or
switching-off, can be saved.
0: MOP setpoint will not be stored
1: MOP setpoint will be stored in P1040
P1032 = 1
Inhibit reverse direction of MOP
0: reverse direction is allowed
1: Reverse direction inhibited
P1040 = 5
Setpoint of the MOP
Defines the setpoint [Hz] of the motorized potentiometer (MOP).
5-36
Operating Instructions, 11/2006, A5E00766042B AA