Functions
8.15 Brake functions
8.15.2

Electronic brakes (only with PM240)

Overview
The SINAMICS G120 inverter has three electronic braking technologies:
● DC braking
● Compound braking
● Dynamic braking
These brakes can actively brake the motor and avoid a possible DC link overvoltage
condition. The figure below shows the inter-dependency of the electronic braking functions.
Figure 8-56
8.15.2.1

DC braking

Data
Parameter range:
Warnings:
Faults:
Function chart number:
Description
The motor decelerates along a parameterized braking ramp if an OFF1 or OFF3 command is
output. A "flat" ramp must be selected so that the inverter is not tripped (shutdown) due to
the high regenerative energy which would cause a DC link overvoltage condition. The DC
brake should be activated while the OFF1 or OFF3 command is present if the motor is to be
braked faster. For DC braking, instead of continually reducing the output frequency/voltage
during the OFF1 or OFF3 phase, from a selectable frequency, a DC voltage/current is input
(refer to sequence 1).
The motor can be brought to a standstill in the shortest time using DC current braking (DC
brake). DC braking is selected as follows:
8-82
Inter-dependency of electronic brakes
P1230, P1233
P1232, P1234
r0053 Bit00
-
-
-
Operating Instructions, 11/2006, A5E00766042B AA