Table 8-29 Automatic Restart - Siemens SINAMICS G120 Operating Instructions Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Functions
8.16 Automatic restart
Table 8-29
Automatic restart
P1210
Blackout
0
---
1
Fault acknowledge
2
Fault acknowledge
+ restart
3
Fault acknowledge
+ restart
4
Fault acknowledge
+ restart
5
Fault acknowledge
+ restart
6
Fault acknowledge
+ restart
Caution
*
Automatic restart with external 24 V supply
)
If the Control Unit is powered by an external 24 V supply and the mains line supply fails, the
Power Module will lose power, but the Control Unit will remain active. If this situation occurs
then the Control Unit will not perform an automatic restart. This situation could result in the
inverter being in an undetermined state and may not react as predicted.
Source command for automatic restart
The automatic restart function has been designed to ignore command source time-outs. That
is, if the command sources is, for example, a PLC or through USS communications and the
PLC or USS times-out an automatic restart will not be initiated.
The number of start attempts is specified using parameter P1211. The number is internally
decremented after each unsuccessful attempt. After all attempts have been made (as
specified in parameter P1211), automatic restart is cancelled with the message F0035. After
a successful start attempt, the counter is again reset to the initial value.
8-94
ON always active
Fault F0003 for
Brownout
---
---
See Caution *
Fault acknowledge
+ restart
Fault acknowledge
+ restart
See Caution *
Fault acknowledge
+ restart
All other faults for
Blackout
---
---
---
---
---
---
Fault acknowledge
Fault acknowledge
+ restart
+ restart
---
---
---
Fault acknowledge
+ restart
Fault acknowledge
Fault acknowledge
+ restart
+ restart
Operating Instructions, 11/2006, A5E00766042B AA
Inverter ON and no
RUN command
All faults + F0003
Brownout
---
Fault acknowledge
---
---
---
Fault acknowledge
Fault acknowledge