Note
MMC for "automatic download"
For an automatic download always the file clone00.bin will be used.
The user has to take care, that clone00.bin (saved as "clone00.bin" with STARTER via PC or
via setting P0804 = 00 with the OP) is available on the MMC, used for an automatic
parameter download at start-up. If clone00.bin does not exist drive will fail with F0061
Successful automatic download
After a successful automatic download, F0395 will be displayed.
● In case of a standard CU a confirmation is necessary.
● In the case of CUs with fail-safe functions, an acceptance test must be performed.
Confirmation
On standard CUs the current parameter set needs to be checked and confirmed by clearing
F0395. It can be cleared via:
● Digital input or PLC signal (depends on the settings of P0700)
● setting P7844 = 0.
● Via the
Acceptance test
On CUs with fail-safe functions it is necessary to do an acceptance test (refer to the "Fail-
safe functions" section in this manual). To clear F0395 on CUs with fail-safe functions the
following procedure has to be followed:
● P0010 = 30
● P9761 = safety password
● P7844 = 0
● Carry out acceptance test
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
button on the OP
Warning
The user is responsible for ensuring that the parameters held in the CU are the correct
parameters for their application.
Operation
6.3 Start-up Behavior
6-7