Warning
For series commissioning, all of the communication interfaces as well as also the digital and
analog interfaces are re-initialized. This results in a brief communications failure or causes
the digital outputs to switch.
Potentially hazardous loads must be carefully secured before starting a series
commissioning.
Potentially hazardous loads can be secured as follows before starting series commissioning:
• Lower the load to the floor, or
• Clamp the load using the motor holding brake.
Note
Upload
Before the upload starts, the parameters will be copied from RAM to EEPROM
Manual and automatic download
With a manual download all necessary parameters excluding the fail-safe parameters (only
with CUs with fail-safe functions) are downloaded into the inverter. A manual download can
be triggered by the customer as described in the following.
With an automatic download even the fail-safe parameters are downloaded into the inverter.
An automatic download can only be performed with an MMC.
An automatic download can be performed at Start-up or by swapping an inverter component
(CU or PM), details are described in the following sections and in the chapter "Operation" of
this manual.
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
Commissioning (software)
5.7 Commissioning modes
5-45