Functions
8.18 Fail-safe functions
Case 5.1:
8-122
Frequency setpoint > SLS monitoring (p9691/p9891) primary fault
Initiation of SLS =>
When standstill detection is
reached =>
Deactivation of SLS =>
• Ramp monitoring activated
• SLS-LED flashing
• Frequency setpoint deactivated
• Ramp down with SS1 to standstill
detection
• Frequency setpoint inactive
• LSTO activated
• No action
• To start again, LSTO must be
acknowledged and a new on command is
necesarry to ramp up to frequency
setpoint.
Operating Instructions, 11/2006, A5E00766042B AA