Table 4-3 Permissible Cable Length For One Segment - Siemens SINAMICS G120 Operating Instructions Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing/Mounting
4.3 Connecting a CU240S DP or CU240S DP-F via PROFIBUS DP
Maximum cable lengths
The PROFIBUS system can handle up to 126 stations. To run all these stations the
PROFIBUS system is divided into segments. All segments have to be connected via
repeater. The maximum number of stations on any segment must not exceed 32.
The maximum cable lengths are dependent on the baud rate (transmission speed). The
maximum cable lengths specified in the table below can be guaranteed only with PROFIBUS
bus cables (for example, Siemens PROFIBUS bus cable, order number 6XV1830-0EH10).
Table 4-3
Baud rate
9.6 kbaud ... 187.5 kbaud
500 kbaud
1.5 Mbaud
3 Mbaud ... 12 Mbaud
∗ Repeaters can be installed to increase the length of a segment.
Cable installation rules
During installation the bus cable must not be:
● twisted
● stretched or
● compressed.
Supplementary constraints as regards electromagnetic compatibility must also be observed.
4-12
Permissible cable length for one segment
Max. cable lengths for one segment
1000 m (3280 ft)*
400 m (1312 ft)*
200 m (656 ft)*
100 m (328 ft)*
Operating Instructions, 11/2006, A5E00766042B AA
Control Units CU240S

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu240sCu240s dpCu240s dp-f