Siemens SINAMICS G120 Operating Instructions Manual page 94

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Commissioning (software)
5.7 Commissioning modes
Frequency setpoint via fixed frequency (P1000 = 3)
Parameter
Description (Parameter name and factory setting (if not variable) in bold)
P1016 = 1
Fixed frequency mode, defines
the selection method for fixed
frequencies.
1: direct selection
2: binary coded
P1001 = 0
Fixed frequency 1, (FF1)
Value given in Hz.
P1002 = 5
Fixed frequency 2
P1003 = 10
Fixed frequency 3
P1004 = 15
Fixed frequency 4
P1005 = 20
Fixed frequency 5
P1006 = 25
Fixed frequency 6
P1007 = 30
Fixed frequency 7
P1008 = 35
Fixed frequency 8
P1009 = 40
Fixed frequency 9
P1010 = 45
Fixed frequency 10
P1011 = 50
Fixed frequency 11
P1012 = 55
Fixed frequency 12
P1013 = 60
Fixed frequency 13
P1014 = 65
Fixed frequency 14
P1015 = 65
Fixed frequency 15
P1020 = 722.3
Fixed frequency selection - Bit 0
Selects DI3 for FF selection
P1021 = 722.4
Fixed frequency selection - Bit 1
Selects DI4 for FF selection
P1022 = 722.5
Fixed frequency selection - Bit 2
Selects DI5 for FF selection
P1023 = 722.6
Fixed frequency selection - Bit 3
Selects DI6 for FF selection
5-38
The fixed frequency can be selected via four digital
inputs (default DI3 ... DI6).
Fixed frequences via direct selection (P1016 = 1):
With the default settings additional combinations as
follows are possible:
Fixed frequences via binary coded selection
(P1016 = 2):
With binary coded selection each frequency, set in one
of the parameters P1002 ... P1015 can be directly
selected.
Fixed Frequency
FF-
selected via
Par
DI3 (P1020 =722.3)
P1001
DI4 (P1021 =722.4)
P1002
DI5 (P1022 =722.5)
P1003
DI6 (P1023 =722.6)
P1004
DI3, DI4
P1005
DI4, DI5
P1006
DI5, DI6
P1007
DI3, DI5
P1008
DI4, DI6
P1009
DI3, DI6
P1010
DI3, DI4, DI5
P1011
DI4, DI5, DI6
P1012
DI3, DI5, DI6
P1013
DI3, DI4, DI6
P1014
DI3, DI4, DI5, DI6
P1015
Operating Instructions, 11/2006, A5E00766042B AA
FF-default
setting
[Hz]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
65
Control Units CU240S
Setting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu240sCu240s dpCu240s dp-f

Table of Contents