Commissioning (software)
5.7 Commissioning modes
Reset to the factory setting
Parameter or action
P0003 = 1
P0004 = 0
P0010 = 30
P0970 = 1
BUSY (on OP)
Progress bar (STARTER)
Note
The following parameters will not be changed with a factory reset:
• P0014 Store mode
• P0100 Europe / North America
• P0201 power stack code number
• Communication parameters (USS and PROFIBUS settings)
• Data depending on actual Power module
5-60
Warning
Fail-safe parameters
When using Standard CUs, only the factory reset with P0970 = 1 must be taken into
account.
When using CUs with fail-safe functions two reset methods are available:
• P0970 = 1 resets only non fail-safe function relating parameters (application
parameters).
If a factory reset with P0970 =1 is performed on a Control Unit with fail-safe functions
all application parameters will be reset, previous parameters settings regarding fail-
safe functions remain unchanged. This means, no acceptance test has to be
performed.
• P0970 = 10 (password protected) resets only fail-safe function relating parameters
If parameters regarding fail-safe functions must be changed, an acceptance test has
to be performed.
Description (Parameter name and factory setting (if not variable) in bold)
User access level*
1: Standard: Allows access into most frequently used parameters.
Parameter filter
0: All parameters
Commissioning parameter*
30: Factory setting, parameter transfer
Factory reset*
1: Parameter reset to the default values
The inverter carries-out a parameter reset (duration, approx. 10 s) and then automatically
exits the reset menu and sets
P0970 = 0: Disabled
P0010 = 0: Ready