A.3 EMC Overall Performance
A.3

EMC Overall Performance

EMC Emissions
The SINAMICS G120 drives have been tested in accordance with the emission requirements
of the category C2 (domestic) environment.
Table A-2
EMC Phenomenon
Conducted Emissions
Radiated Emissions
Note
To achieve this performance the default switching frequency should not be exceeded.
In order to achieve conducted emissions to EN 55011 Class B there is a range of PM240
external filter options available.
Achieving radiated emissions to EN 55011 Class B is largely dependent on the drive being
correctly installed inside a metallic enclosure. The limits will not be met if the drive is not
enclosed or installed in accordance with good EMC practices.
Harmonic Currents
The harmonic current emissions from the SINAMICS G120 drives is as follows:
Table A-3
Rating
FSA ... FSF
(400 V, 370 W ... 90 kW)
Note
Units installed within the category C2 (domestic) environment require connection to the
public low-voltage power supply network. Please contact your local supply network provider.
A-4
Conducted & Radiated Emissions
Standard
EN 55011
EN 55011
Harmonic Currents
Typical Harmonic Current (% of rated input current)
5th
73
7th
11th
13th
52
25
23
Operating Instructions, 11/2006, A5E00766042B AA
Level
Class A
Class A
17th
19th
23rd
22
15
12
Control Units CU240S
25th
10