Device read
Device read random points
random points
(Default: 0 point)
*2
Device write
Device write random points
random points
(Default: 0 point)
*2
*1
Each of [GOT Station] set in the communication detail setting
and [Station] set in the Ethernet setting must be set to
different station numbers.
8.3.4 Ethernet setting
*2
Pay attention to the following items for read/write points.
• Set the points to be processed at one-time
communication.
• The point is in word device units. The point is to be 16
times of the set value for the bit device.
• The points could be less than the set value when UDP
protocol or ASCII code are used.
• Refer to the following Technical News for details.
List of SLMP-compatible Equipment Validated to
Operate with the GOT2000 Series (GOT-A-0085)
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
8.3.3
0 to 192 points
0 to 160 points
Item
GOT
IP Address
Subnet Mask
Default
Gateway
Peripheral S/W
Communication
Port No.
Transparent
Port No.

GOT Ethernet Setting

Description
Set the IP address of the GOT.
0.0.0.0 to
(Default: 192.168.3.18)
255.255.255.255
Set the subnet mask for the sub
network.(Only for connection via
router)
0.0.0.0 to
If the sub network is not used, the
255.255.255.255
default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the GOT
0.0.0.0 to
is connected. (Only for
255.255.255.255
connection via router)
(Default: 0.0.0.0)
1024 to 5010,
Set the GOT port No. for the S/W
5014 to 65534
communication.
(Except for 5011,
(Default: 5015)
5012, 5013, and
49153)
1024 to 65534
Set the GOT port No. for the
(Except for 5011 to
transparent function.
5013 and 49153 to
(Default: 5014)
49170)
8. SLMP CONNECTION
8.3 GOT Side Settings
Range
8
8 - 5