Precautions when preparing a cable
(1) Cable length
The distance between the GOT and the PLC of
connection diagram 1), 2) and 3) must be 1200 m or
less.
The length of the RS-422 connection diagram 4) or RS-
422 connection diagram 5) must be 30m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
Connecting terminating resistors
(1) GOT side
When connecting a microcomputer to the GOT, a
terminating resistor must be connected to the GOT.
(a) For GT27,GT25,GT23
Set the terminating resistor setting switch of the
GOT main unit to "Disable".
(b) For GS
Set the terminating resistor selector to "330 ".
For the procedure to set the terminating resistor,
refer to the following.
1.4.3 Terminating resistors of GOT
2. MICROCOMPUTER CONNECTION (SERIAL)
2.3 Connection Diagram