Communication Detail Settings - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal microcomputers, modbus/fieldbus products, peripherals
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

17.4.2 Communication detail settings

Make the settings according to the usage environment.
(1) Video Setting
Item
Description
Video Input
Set the video input signal.
*1
(Default: NTSC)
Signal
*2
Set the video resolution.
Video Resolution
*1
When NTSC format is selected, the resolution is fixed to
640 480.When PAL format is selected, the resolution is
fixed to 768 576.
*2
For GT2710-V and GT2708-V, the resolution is fixed to
640 480.
(2) IP Address Setting for Multimedia Unit
Set the network settings for connecting from the
multimedia unit via Ethernet.
Item
Description
Set the IP address of the
IP Address
multimedia unit.
(Default: 192.168.3.51)
Set the subnet mask for the sub
network. (Only for connection via
Subnet Mask
router) If the sub network is not
used, the default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway on the side to
Default
which the multimedia unit is
Gateway
connected. (Only for connection
via router)
(Default: 0.0.0.0)
POINT
POINT
POINT
Network settings with the utility
The network setting can be changed on the Utility's
[Communication setting] after writing [Communication
Settings] of project data.
For details on the Utility, refer to the following manual.
Range
NTSC, PAL
640 480,
720 480,
768 576
Range
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255