Mitsubishi Electric GOT2000 Series Connection Manual page 247

Graphic operation terminal microcomputers, modbus/fieldbus products, peripherals
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Address
GT Designer3 converts the device numbers into
decimal format according to the address map of the
®
MODBUS
/RTU equipment to be used.
The table below shows the representations on the
®
MODBUS
/RTU communication protocol and GT
Designer3.
MODBUS/RTU Communication protocol
Function code to be
used
Device name
Read
Write
0x05
Coil
0x01
0x0F
Input relay
0x02
-
Input register
0x04
-
Holding
0x06
0x03
register
0x10
Extension file
0x14
0x15
register
POINT
POINT
POINT
Address conversion example
When monitoring the holding register's address
"1234H", GT Designer3 displays "4*****" since GT
Designer3 processes the internal conversion in
decimal format as follows:
GT Designer3 converts the holding register's address
"1234H" to "04660" in decimal format.
Then, "+1" is added to this decimal address since the
holding register's address on GT Designer3 always
starts from "1."
Therefore, the holding register's address "1234H" is
displayed as "404661" on GT Designer3.
Holding register
"4 04660" +1
Representation on GT
Designer3
Address
0000
000001
0001
000002
to
to
FFFE
065535
FFFF
065536
0000
100001
0001
100002
to
to
FFFE
165535
FFFF
165536
0000
300001
0001
300002
to
to
FFFE
365535
FFFF
365536
0000
400001
0001
400002
to
to
FFFE
465535
FFFF
465536
0000
600000
0001
600001
to
to
270E
609998
270F
609999
1234H
"404661"
MODBUS communication control function on
the GS device
(1) Function overview
This function is to prevent the communication response
delay that occurs because the devices on the
MODBUS network differs from each other in network
specification.
This function is effective for the MODBUS network
conditions as described below:
• When only a part of function codes is supported
(Example: "0F" is not supported)
• When the maximum transfer size of function code is
small (Example: The maximum number of coil read
times is 1000)
(2) Communication setting
When the MODBUS/RTU communication driver is
assigned to multiple channel numbers using the multi-
channel function, the following cases are possible. The
communication settings are shared between the
assigned multiple channel numbers, or the individual
communication setting is configured to a specific
channel number.
By setting the device GS579, either the GS device used
for sharing communication settings (GS570 to GS576)
or the GS device used for individual communication
setting (GS590 to GS617) is validated.
GS
Description
device
Validity of
GS579
setting channel
number
For details of GS devices (GS570 to GS576) and GS
devices (GS590 to GS617), refer to the next page.
5. MODBUS(R)/RTU CONNECTION
5.5 MODBUS(R)/RTU Equipment Side Setting
Set value
Bit0:
0
Configure the Ch1 communication
settings between GS570 to
GS576.
1
Configure the Ch1 communication
settings between GS590 to
GS596.
Bit1:
0
Configure the Ch2 communication
settings between GS570 to
GS576.
1
Configure the Ch2 communication
settings between GS590 to
GS603.
Bit2:
0
Configure the Ch3 communication
settings between GS570 to
GS576.
1
Configure the Ch3 communication
settings between GS604 to
GS610
Bit3:
0
Configure the Ch4 communication
settings between GS570 to
GS576.
1
Configure the Ch4 communication
settings between GS611 to
GS617.
5 - 15
5