18.3.2 Communication detail settings

Item
Description
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 9600bps)
Set this item when change the data
length used for communication with
Data Bit
the connected equipment.
(Default: 8bits)
Specify the stop bit length for
Stop Bit
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
Parity
during communication.
(Default: Even)
Set whether or not to perform a sum
Sum Check
check during communication.
(Default: Done)
Set the number of retries to be
performed when a communication
timeout occurs.
Retry
When receiving no response after
retries, the communication times
out. (Default: 0time)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Set this item to adjust the
transmission timing of the
Delay Time
communication request from the
GOT.
(Default: 0ms)
Select the communication format.
(Default: 15)
Dedicated protocol
• Format 10 (LS Industrial Systems
Co., Ltd. LSR)
• Format 11 (MARS TOHKEN
Format
SOLUTION CO.LTD. ICU-60S)
1
• Format 12*
SOLUTION CO.LTD. ICU-215
(Mifare))
Nonprocedural protocol
• Format 15
*1
GT21 does not support Format 12.
Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
Yes or No
0 to 5times
3 to 30sec
0 to 3000ms
10/11/12/15
(MARS TOHKEN
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manuals.
User's Manual of GOT used.
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
18. RFID CONNECTION
18.3 GOT Side Settings
18
18 - 5