6.3 GOT Side Settings

6.3.1
Setting communication
interface (Communication
settings)
Set the channel of the equipment to be connected to the
GOT.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: MODBUS
• Controller Type: MODBUS
• I/F: Interface to be used
• Driver: MODBUS/TCP, Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

6.3.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be set and
confirmed in [I/F Communication Setting].For details,
refer to the following.
1.1.2 I/F communication setting
6 - 4
6. MODBUS(R)/TCP CONNECTION

6.3 GOT Side Settings

Click!
[Controller Setting] from the
6.3.2
Communication detail settings
Make the settings according to the usage environment.
3.
4.
Item
Set the network No. of the GOT.
GOT Net No.
(Default: 1)
Set the station No. of the GOT.
*1
GOT Station
(Default: 1)
Set the GOT IP address, subnet
GOT Ethernet
mask, default gateway, peripheral
Setting
S/W communication port No.,
transparent port No
Set the GOT port No. for the
GOT
connection with the Ethernet
Communication
module.
Port No.
(Default: 5020)
Specify the time period from the
GOT startup until GOT starts the
Startup Time
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination
Delay Time
PLC.
(Default: 0ms)
Select the steps to store two words
32bit Storage
(32-bit data).
(Default: LH Order)
Set whether to use the function
FunctionCode[
code [0F].
0F]
(Default: Used)
Set whether to use the function
FunctionCode[
code [10].
10]
(Default: Used)
Set the read points of the coil.
Coil read times
(Default: 1000 points)
Set the read points of the input
Input relay
relay.
read times
(Default: 1000 points)
Description
Range
1 to 239
1 to 247
6.3.3GOT
Ethernet Setting
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
3 to 255sec
3 to 90sec
0 to 10000
(
10 ms)
LH Order/HL Order
Used/Unused
Used/Unused
1 to 2000 (points)
1 to 2000 (points)