Terminal
Input /
symbol
output
Multifunction programmable analog output. Default setting: output
frequency.
FM
Output
The function can be changed to meter option (0-1mA), 0-10Vdc voltage
or 0-20mAdc (4-20mA) current output by parameter f681 setting.
Resolution Max. 1/1000.
Output
24Vdc power output, by changing SW1 to SINK or SOURCE side.
P24
This terminal can be used as a common terminal when an external
Input
power supply is used by changing SW1 to PLC side.
DC power input terminal for operating the control circuit. Connect a
Input
control power backup device (option or 24Vdc power supply) between
+SU and CC.
+SU
It is used with STO for safety function.
+SU and STO terminals are short-circuited by metal bar and the inverter
Output
is put into a standby state at default setting. When the circuit between
them is opened, the motor is coasting stop.
When +SU and STO are short-circuited, the inverter is put into a standby
state. (Default setting) And when the circuit between them is opened, the
STO
motor is coasting stop. These terminals can be used for inter lock.
Input
This terminal is not a multifunction programmable input terminal.
Note 2)
It is a terminal with the safety function that complies with SIL II of the
safety standard IEC61508.
Multifunction programmable open collector output. Default setting detect
and output speed reach signal.
Multifunction output terminals to which two different functions can be
assigned.
OUT
Output
The NO terminal is an equipotential terminal. It is isolated from the CC
NO
terminal.
By changing parameter f669 settings, these terminals can also be
used as multifunction programmable pulse train output terminals.
Function
Q-9
E6582175
Electrical
specifications
1mAdc full-scale
ammeter or
QS60T(option)
0-20mA (4-20mA)
DC ammeter
Permissible load
resistance:
600Ω or less
0-10V DC volt
meter
Permissible load
resistance:
1kΩ or more
24Vdc-100mA
-
Voltage:
24Vdc±10%
Current:
1A or more
-
Independently of
SW1
ON: DC17V
or more
OFF: DC12V
or less
(OFF: Coast stop)
Open collector
output
24Vdc-100mA
To output pulse
trains,
a current of 10mA
or more needs to
be passed.
Pulse frequency
range:
10~2kpps
17