3.2.1
How to run and stop
[Example of  setting procedure]
Panel operation
LED display
MODE
auh
cmod
0cmod
(1) Run and stop using the panel keypad (cmod=1)
RUN
Use the
and
: Motor runs.
RUN
●The direction of rotation is determined by the setting of parameter  (forward run, reverse run selection).
(: forward run, : reverse run)
●Forward run and reverse run are switchable with the extension panel (option). Set the parameter fr
(forward run, reverse run selection) to 2 or 3. (Refer to section 6.2.2)
(2) RUN and STOP using external signals (cmod=0): Sink (Negative) logic
Use external signals to the inverter terminal block to start and stop the motor.
Short
and
terminals: run forward
F
CC
Open
and
terminals: slow down and stop
F
CC
Displays the output frequency (operation stopped).

(When standard monitor display selection f710=0 [output frequency])
Displays the first basic parameter [History (auh)].
Turn the setting dial, and select "cmod".
Press the center of the setting dial to read the parameter value.
1
(Standard default: 1).
Turn the setting dial to change the parameter value to 0 (terminal
0
block).
Press the center of the setting dial to save the changed parameter.
cmod and the parameter set value are displayed alternately.
STOP
keys on the panel keypad to start and stop the motor.
: Motor stops.
STOP
Frequency
C-5
Operation
Slow down
and stop
F-CC
E6582175
3
ON
OFF