(2) [f105 = 1 (Stop)]: If an F command and an R command are entered simultaneously,
6
6.6.2
f107 : Analog input terminal selection (VIB)
 Function
[Parameter setting]
Title
f107
● f107=0 : Input 0 to +10Vdc to VIB-CC terminals.
Resolution is maximum 1/1000 between 0 to +10Vdc.
● f107=1 : Input -10 to +10Vdc to VIB-CC terminals.
Resolution is maximum 1/2000 between -10 to +10Vdc.
the motor will deceleration stop.
Output frequency [Hz]
Setting frequency
0
Forward run command
Reverse run command
Changing the voltage range of VIB terminal
This parameter allows you to choose the voltage signal input for the VIB terminal.
Function
Analog input terminal
selection (VIB)
Adjustment range
0: 0-+10V
1: -10-+10V
F-30