6.5.2
Output of designated frequency reach signal
f102 : Speed reach detection band
 Function
When the output frequency becomes equal to the setting by designated frequency  f102, an ON
or OFF signal is generated.
[Parameter setting]
Parameter setting of designated frequency and detection band
Title
Speed reach detection band
f102
Parameter setting of output terminal selection
Title
Function
Output terminal
f131
selection 2A (OUT)
Setting value 7 is reverse signal.
Note: Set f132 to output to FLA-FLC-FLB terminals and f130 to RY-RC terminal.
Designated frequency  
Designated frequency  
Output frequency attainment signal
: OUT-NO terminals
Inversion of output frequency
attainment signal
Function
0.0-fh (Hz)
Adjustment range
0-255
(Refer to section 11.7.)
Output frequency [Hz]
Setting frequency
0
F-27
Adjustment range
Default setting
6: RCH (Output frequency attainment signal
(acceleration/deceleration completed))
Time [s]
ON
OFF
ON
OFF
E6582175
Default setting
2.5
6