 = (Variable torque characteristic), = (Temperature estimation)
This parameter adjusts automatically overload protection, predicting the inverter internal temperature rise.
(diagonally shaded area in the figure below)
time [s]
f631=0
60
0
Note 1: The rated output current of inverter is changed by setting of aul=1 or 2.
Refer to page L-1 about each rated output current.
Note 2: Parameter aul is displayed as "0" during reading after this is set.
Note 3: Present setting of inverter overload characteristic can be confirmed by status monitor.
Refer to monitor "Overload and region setting" of section 8.2.1.
6) Overload alarm level f657
When the motor overload level reaches to f657 setting value (%) of overload trip (ol2) level, "l" will be
displayed on the left side digit and the "l" and output frequency monitor will be blinking alternately on
overload alarm status.
Overload alarm signal can be output from output terminal.
[Parameters settings]
Title
Function
f657
Overload alarm level
[Example of setting]: Assigning the overload alarm to the OUT terminal.
Title
Function
Output terminal selection 2A (OUT)
f131
17 is reverse signal.
105%
120%
100%: Inverter rated output current
Adjustment range
10-100 (%)
Adjustment range
0-255
E-15
E6582175
Monitored output current [%]
Default setting
50
Setting
16: POL
5