Toshiba Tosvert VF-S15 Instruction Manual page 246

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

6.34.8 Cancel the operation command
f719 : Selection of operation command clear
 Function
Parameter
=
=
=
=
6
Operation command retained :
Inverter restarts due to clearing coast stop at coast stop.
Inverter restarts due to supply power source again when the under voltage in main circuit alarm ()
occurs.
Operation command cleared :
Inverter doesn't restart after coast stop or occurring the under voltage in main circuit alarm ().
Press RUN key to operate again in panel operation.
Switch to ON the operation command in RS485 communication operation.
Title
f719
[Setup example of input terminal]
When it is assigned to the RES terminal.
Title
f113 
f113 
Setting value 7, 97 are reverse signal.
This parameter allows you to select operation command retained or operation command cleared, when
coast stop occurs due to standby terminal function (ST), coast stop command terminal function (FRR),
and when under voltage in main circuit alarm ( moff ) occurs, during panel operation or RS485
communication operation.
At coast stop
setting
Operation command
cleared
Function
Selection of operation
command clear
Function
Input terminal selection 3A
(RES)
Input terminal selection 3A
(RES)
At under voltage
in main circuit alarm ( moff )
Operation command retained
Operation command retained
Operation command cleared
Operation command cleared
Adjustment range
0: Clear at coast stop and retained at
moff .
1: Retained at coast stop and moff .
2: Clear at coast stop and moff .
3: 2+ clear when cmod is changed
Adjustment range
0-203
0-203
F-134
E6582175
comd
is changed
Operation command
retained
Default setting
1
Setting
6: ST (Standby)
96: FRR (Coast stop command)