Signal Output - Toshiba Tosvert VF-S15 Instruction Manual

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

6.5

Signal Output

6.5.1 Output running signal and braking signal (Low-speed signal)
Refer to section 7.2.2 for output terminal function.
f100 : Low-speed signal output frequency
 Function
[Parameter setting]
Title
6
f100
 Output terminal setting
When the output frequency become f100 or more, an ON signal will be generated. This signal can
be used as an electromagnetic brake excitation/release signal. (Refer to "Motors with a brake" in
section 1.4.1 for application.)
This signal can also be used as an operation signal when f100 is set to 0.0Hz, because an ON
signal is put out if the inverter is in output state.
● Output from the relay output terminal RY-RC. (Default)
Output from the terminal FLA-FLB-FLC and OUT are possible by the parameter settings.
Function
Low-speed signal output frequency
Output frequency
Setting frequency
Low-speed detection signal :
OUT-NO terminals
Inversion of low-speed
detection signal
Low-speed signal (ON signal) is output from RY-RC terminal by default setting.
Change this setting to invert the polarity of the signal.
[Parameter setting]
Title
Function
Output terminal selection 1A (RY-RC)
f130
Setting value 5 is reverse signal.
Note) Set f132 to output to FLA-FLC-FLB terminals and f131 to OUT terminal.
Adjustment range
0.0 - fh (Hz)
[Hz]

0
Adjustment range
(Refer to section 11.7)
F-26
E6582175
Default setting
0.0
Time [s]
ON
OFF
ON
OFF
Default setting
4: LOW (Low-
0-255
speed detection
signal)