Applied Operations By An I/O Signal (Operation From The Terminal Block - Toshiba Tosvert VF-S15 Instruction Manual

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

7.2
Applied operations by an I/O signal (operation from
the terminal block)
Input terminal sink and source logic are set by using slide switch SW1.
7.2.1
This function is used to send a signal to the
input terminal from an external programmable
controller to operate or configure the inverter.
The ability to select from a variety of functions
allows for flexible system design.
Default settings of slide switch SW1and SW2 are
as follows;
SW1: PLC side, SW2: VIB side and S3 side.
Refer to page B-11 to 13 for details.
7
 Settings for the logic input terminal function
Terminal
symbol
F
R
RES
S1
S2
S3
VIB
VIA
VIA
VIB
F to VIB
Input terminal function
(sink logic)
Title
Function
 Input terminal selection 1A (F)
 Input terminal selection 1B (F)
 Input terminal selection 1C (F)
 Input terminal selection 2A (R)
 Input terminal selection 2B (R)
 Input terminal selection 2C (R)
 Input terminal selection 3A (RES)
 Input terminal selection 3B (RES)
 Input terminal selection 4A (S1)
 Input terminal selection 4B (S1)
 Input terminal selection 5 (S2)
Logic
input
/ pulse
f146
selection (S2)
 Input terminal selection 6 (S3)
Logic input / PTC input selection (S3)
f147
 Input terminal selection 7 (VIB)
 Input terminal selection 8 (VIA)
 Analog/logic input selection (VIA/VIB)
 Input terminal response time
[Control terminal block]
SW2
VIB
PTC
PP
VIA
VIB
CC
VIC
OUT
CC
NO
P24
F
Adjustment range
0-203 Note 1)
0-203 Note 1)
0-203 Note 1)
0-203 Note 1)
0-203 Note 3)
train input
0: Logic input
1: Pulse train input
0-203 Note 4)
0: Logic input
1: PTC input
0-203 Note 5)
8-55 Note 6)
0-4
1-1000 (ms) Note 7)
G-2
E6582175
SW1
SOURCE
SINK
S4
S3
PLC
S3
FM
FLA
FLC
FLB
RY
STO
R
CC
+SU
S2
RES
S1
Default setting
2 (F)
0 (No function)
0 (No function)
4 (R)
0 (No function)
0 (No function)
8 (RES)
0 (No function)
10 (SS1)
0 (No function)
12 (SS2)
0
14 (SS3)
0
16 (SS4)
24 (AD2)
0
1
RC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents