Toshiba Tosvert VF-S15 Instruction Manual page 229

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

6.29.17 Number of starting alarm
f648 : Number of starting alarm
 Function
Counting the number of starting, when it will reach the value of parameter f648 setting, it will be
displayed and alarm signal is output.
[Parameter setting]
Title
Number of starting alarm
f648
● "0.1" displayed on the monitor refers to 1000 times, and therefore "1.0" denotes 10000 times.
Ex.: 38.5 displayed on the monitor = 385000 (times)
● Display of number of starting alarm information
Number of starting alarm information in the Status monitor mode allows you to check on the time of
replacement. (Refer to chapter 8)
An example of display:
● Output of number of starting alarm signal
The number of starting alarm is assigned to the output terminal.
Setup example) When the number of starting alarm is assigned to the OUT terminal
Title
f131  Output terminal selection 2A (OUT)
Setting value 163 is reverse signal.
● The number of starting, forward number of starting and reverse number of starting until present time can be
monitored by setting status monitor mode. (Refer to chapter 8)
● The monitor value of the number of starting, number of forward run and number of reverse run are reset to
0 (zero) by setting typ = 12 (number of starting clear). (Refer to section 4.3.2)
Function
0.0-999.0 (10000 times)
 
Function
Adjustment range
0-255
F-117
Adjustment range
Default setting
Setting
162: NSA (Number of
starting alarm)
E6582175
999.0
6