Toshiba Tosvert VF-S15 Instruction Manual page 252

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

 Settings for speed command via communication
Title
fmod 
 Communication function parameters (2-wire RS485 communication)
Communication speed, parity, inverter number, and communication error trip time settings can be changed
via panel operations or communication.
[Parameter setting]
Title
f800
f801
f802
f803
6
f804 
f805  Communication waiting time
f806 
f808 
f810 
f811 
f812 
f813 
f814 
f829
Function
Frequency setting mode
selection
Function
Baud rate
Parity
Inverter number
Communication time-out time
*1
Communication time-out action
*1
Setting of master and slave for
communication between inverters
Communication time-out
detection condition
Communication command point
selection
Communication command point 1
setting
Communication command point 1
frequency
Communication command point 2
setting
Communication command point 2
frequency
Selection of communication
protocol
F-140
Adjustment
Standard
range
defaults
0 - 14
0 (Setting dial 1)
Adjustment range
3: 9600bps
4: 19200bps
5: 38400bps
0: No parity
1: Even parity
2: Odd parity
0-247
0: Disabled
0.1-100.0 (s)
0: Alarm only
1: Trip (Coast stop)
2: Trip (Deceleration stop)
0.00-2.00
0: Slave (0 Hz command issued in
case the master inverter fails)
1: Slave (Operation continued in
case the master inverter fails)
2: Slave (Emergency stop tripping
in case the master inverter fails)
3: Master (transmission of
frequency commands)
4: Master (transmission of output
frequency signals)
0: Valid at any time
1: Communication selection of
fmod or cmod
2: 1  during operation
0: Disabled
1: Enabled
0-100
0.0- fh
0-100
0.0- fh
0: Toshiba inverter protocol
1: Modbus RTU protocol
E6582175
Setting example
4 (RS485
communications)
Default setting
4
1
0
0.0
0
0.00
0
1
0
0
0
100
*2
0