Toshiba Tosvert VF-S15 Instruction Manual page 293

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

Voltage
class
3 phase
240V
class
1 phase
240V
class
3 phase
500V
Class
*1: For Japan: JEAC8001-2005 compliant
10
Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 (Single-phase models are R/L1
Note 2: For the control circuit, use shielded wires 0.75 mm
Note 3: For grounding, use wires with a size equal to or larger than the above.
Note 4: The wire sizes specified in the above table apply to HIV wires (copper wires shielded with an insulator
Note 5: In case of aul=2 setting, contact your Toshiba distributor for wire size.
Wire size (mm
Applicable
Braking resistor
motor
(optional)
(kW)
IEC
For Japan
Compliant
*1
0.4
1.5
2.0
0.75
1.5
2.0
1.5
1.5
2.0
2.2
1.5
2.0
4.0
2.5
2.0
5.5
4.0
2.0
7.5
6.0
3.5
11
16
5.5
15
25
14
18.5
25
14
0.2
1.5
2.0
0.4
1.5
2.0
0.75
1.5
2.0
1.5
1.5
2.0
2.2
1.5
2.0
3.0
1.5
2.0
0.4
1.5
2.0
0.75
1.5
2.0
1.5
1.5
2.0
2.2
1.5
2.0
4.0
1.5
2.0
5.5
1.5
2.0
7.5
2.5
2.0
11
4.0
2.0
15
6.0
3.5
18.5
10
5.5
and S/L2/N) and the output terminals U/T1, V/T2 and W/T3 when the length of each wire does not exceed
30m. If there is a need to bring the inverter into UL compliance, use wires specified in chapter 9.
with a maximum allowable temperature of 75°C) used at an ambient temperature of 50°C or less.
2
)
Note 4)
Grounding cable
IEC
For Japan
Compliant
*1
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
4.0
3.5
10
5.5
16
5.5
16
8.0
16
8.0
25
8.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
4.0
3.5
4.0
3.5
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
2.5
2.0
4.0
3.5
6.0
3.5
10
5.5
16
5.5
16
5.5
2
or more in diameter.
J-2
E6582175