6.10.4 Setting of frequency with the input from an external logic
 : External logic input - UP response time
 : External logic input - UP frequency steps
 : External logic input - DOWN response time
 : External logic input - DOWN frequency steps
 : Initial value of UP/DOWN frequency
 : Change of the initial value of UP/DOWN frequency
 Function
These parameters are used to set an output frequency by means of a signal from an external device.
[Parameter setting]
Title
External logic input - UP response
f264
time
External logic input - UP frequency
f265
steps
External logic input - DOWN response
f266
time
External logic input - DOWN frequency
f267
steps
f268 Initial value of UP/DOWN frequency
Change of the initial value of
f269
UP/DOWN frequency
This function is valid when the parameter fmod (Frequency setting mode selection 1) = 5 is set.
■ Input terminal settings
Assigning the following functions to the input terminal will allow you to change (up/down) or clear the output
frequency by using the terminal's ON/OFF.
Input terminal function
88
Frequency UP
90
Frequency DOWN
92
Clear frequency UP/DOWN
Each of the following numbers (89, 91, 93) are reverse signals.
Function
0.0 - 10.0 (s)
0.0 - fh (Hz)
0.0 - 10.0 (s)
0.0 - fh (Hz)
 -  (Hz)
0: Not changed
1: Setting of  changed
when power is turned off
Frequency setting increase
Frequency setting decrease
OFF → ON: External logic up/down
F-41
Adjustment range
ON
f268 settings
frequency clear settings
E6582175
Default setting
0.1
6
0.1
0.1
0.1
0.0
1
OFF
Clear
Clear