Toshiba Tosvert VF-S15 Instruction Manual page 195

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

1)
External connection
(1) PID set
value
DC: 0 to 10V
2) Selecting PID set value and feedback value
PID set value and feedback value can be combined as follows for the PID control.
(1) PID set value
PID set value signal selection f389
0: fmod/f207 selected
1: Terminal VIA
2: Terminal VIB
3: fpid
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
Note 1: When setting f389, do not select the same signal used for feedback value.
Note 2: When f389=3 is set, the PID set value is set by the parameter fpid.
fpid can be set by the setting dial in the standard monitor mode.
Please inactivate the frequency setting by the setting dial (fc, Preset-speed frequency)
(Set fmod/f207 to other than 0 or 3, f660 to other than 4, f724 to 0.)
Note 3: Signal is put out when the feedback value matches to the PID set value.
Assign function number 144 or 145 to an output terminal.
PID set value agreement detection range (f167) can also be set.
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
VIA
CC
VIC
CC
(2)Feedback signals DC : 4~20mA
F-83
M
Pressure
transmitter
P
(2) Feedback value
PID control feedback signal selection 
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4 to 6: -
E6582175
6