Toshiba Tosvert VF-S15 Instruction Manual page 194

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

 Function
 Refer to "PID control instruction manual: E6581879" for details.
[Parameter setting]
Title
fpid Set value of PID control
f359
f360
f361 Delay filter
f362
f363
f366
f367 Upper limit of set value
6
f368 Lower limit of set value
f369 PID control feedback signal selection
f372
f373
f380
f389
*1: Default setting value vary depending on the setup menu setting. Refer to section 11.5.
Process control including keeping airflow, pressure, and the amount of flow constant, can be
exercised using feedback signals (4 to 20mA, 0 to 10V) from a detector.
Or, it is also possible to always set 0 for integral and differential at terminal input.
Function
PID control waiting time
PID control
Proportional gain
Integral gain
Differential gain
Process increasing rate (speed type
PID control)
Process decreasing rate (speed type
PID control)
PID forward/reverse characteristics
selection
PID set value signal selection
Adjustment range
f368 -  (Hz)
0-2400 (s)
0: Disabled
1: Process type PID control
2: Speed type PID control
0.0-25.0 (s)
0.01-100.0
0.01-100.0
0.00-2.55
0.0-fh (Hz)
0.0- (Hz)
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4 to 6: -
0.1-600.0 (s)
0.1-600.0 (s)
0: Forward
1: Reverse
0: fmod / f207 selected
1: Terminal VIA
2: Terminal VIB
3: fpid
4: RS485 communication
5: UP/DOWN from external logic
input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
F-82
E6582175
Default setting
0.0
0
0
0.1
0.30
0.20
0.00
60.0 *1
0.0
0
10.0
10.0
0
0