6.26.3 Power running stall continuous trip detection time

f452 : Power running stall continuous trip detection time
• Function
A function for preventing lifting gear from failing accidentally. If the stall prevention function is activated in
succession, the inverter judges that the motor has stalled and trips.
[Parameter setting]
Title
f452 Power running stall continuous trip detection time
f441
Power running torque limit 1 level
Stall prevention level 1
f601
1) In case of overcurrent stall
Output frequency [Hz]
Output current [%]
ot2 trip is occurred if the output current reached the stall prevention level (f601) or more, and this situation
maintain in f452 during power running.
Function

less than

F-97
Adjustment range
0.00-10.00 (s)
0-249%,
250:Disabled
10-199,
200 (disabled)
"2" trip
Time [s]
Time [s]

E6582175
Default setting
0.00
250
150
6