[Trip information]
Error code
Failure code
*
0020
0041
*
0048
*
0049
0010
002E
0011
0012
0013
0014
0015
0016
0017
0018
001A
001B
001C
* This marking trips can be selected valid or invalid by parameters.
Name
Over-torque trip 1
Over-torque reaches to a detection level
during operation.
Over-torque trip 2
Output current reached f601 or more
and maintain in f452 during power
running.
Power running torque reached f441 or
more and maintain in f452 during
power running.
Over-torque /
Power running torque or output current
Overcurrent fault
reached f593 or more and maintain in
f595 during power running.
Power running torque or output current
Small-torque / Small
-current fault
decreased f593 or less and maintain
in f595 during power running.
The cooling fan reaches the end of life or
Overheat
has a fault.
The ambient temperature is too high or
low against the specified ambient
temperature.
The vent is blocked up.
A heat generating device is installed close
to the inverter.
The load is large.
The temperature sensor has a fault.
(When the trip arises, as soon as it is
reset after a while.)
A thermal trip command (input terminal
Thermal fault stop
function: or ) is issued by an
command from
external control device.
external device
Emergency stop
During automatic operation or remote
operation, an emergency stop command
is entered from the operation panel or an
external (terminal or communication) .
EEPROM fault 1
The EEPROM writing error occurs.
EEPROM fault 2
operation is aborted by the power-
off etc.
The EEPROM reading error occurs.
EEPROM fault 3
The EEPROM is defective.
Main unit RAM fault
The control RAM is defective.
The control ROM is defective.
Main unit ROM fault
CPU fault 1
The control CPU is defective.
Communication error
The communication with external devices
is broken off.
Current detector fault
The current detector is defective.
Optional unit fault 1
An optional unit has failed.
(such as a communication option)
Remote keypad
After run signal is activated by RUN key
disconnection fault
of the remote keypad, disconnection is
occurred in 10 seconds or more.
Description
M-3
E6582175
Remedies
Enable (over-torque trip selection).
Check system error.
Reduce the load.
Increase the stall prevention level or
power running torque limit level.
Enable .
Reduce the load.
Check system error.
Enable .
Check system error.
The fan requires replacement if it does
not rotate during operation.
Contact your Toshiba distributor.
Operate at a specified ambient
temperature
Secure sufficient space around the inverter.
Do not place any heat generating device
near the inverter.
Reduce the load.
Reduce f300 : PWM carrier frequency.
Set f136= 1 (Carrier frequency with
automatic reduction)
Contact your Toshiba distributor.
The motor is overheated, so check
whether the current flowing into the motor
exceeds the rated current.
Reset the inverter.
If the emergency stop signal is input,
reset after releasing this signal.
Turn off the inverter, then, turn it again.
If it does not recover from the error,
contact your Toshiba distributor.
Turn off the inverter, then, turn it again,
and then try operation again.
Turn off the inverter, then, turn it again.
If it does not recover from the error,
contact your Toshiba distributor.
Contact your Toshiba distributor.
Contact your Toshiba distributor.
Contact your Toshiba distributor.
Contact your Toshiba distributor.
Check the remote control device, cables,
etc.
Contact your Toshiba distributor.
Check the connection of optional unit.
In case the remote keypad is
disconnected, press STOP key before.
This fault is disabled by f731=1
setting.