Toshiba Tosvert VF-S15 Instruction Manual page 355

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

[Trip information]
Error code
Failure code
*
0020

0041

*
0048

*
0049

0010

002E

0011

0012

0013

0014

0015

0016

0017

0018

001A

001B

001C

* This marking trips can be selected valid or invalid by parameters.
Name
Over-torque trip 1
 Over-torque reaches to a detection level
during operation.
Over-torque trip 2
 Output current reached f601 or more
and maintain in f452 during power
running.
 Power running torque reached f441 or
more and maintain in f452 during
power running.
Over-torque /
 Power running torque or output current
Overcurrent fault
reached f593 or more and maintain in
f595 during power running.
 Power running torque or output current
Small-torque / Small
-current fault
decreased f593 or less and maintain
in f595 during power running.
 The cooling fan reaches the end of life or
Overheat
has a fault.
 The ambient temperature is too high or
low against the specified ambient
temperature.
 The vent is blocked up.
 A heat generating device is installed close
to the inverter.
 The load is large.
 The temperature sensor has a fault.
(When the trip arises, as soon as it is
reset after a while.)
 A thermal trip command (input terminal
Thermal fault stop
function:  or ) is issued by an
command from
external control device.
external device
Emergency stop
 During automatic operation or remote
operation, an emergency stop command
is entered from the operation panel or an
external (terminal or communication) .
EEPROM fault 1
 The EEPROM writing error occurs.
EEPROM fault 2
  operation is aborted by the power-
off etc.
 The EEPROM reading error occurs.
EEPROM fault 3
 The EEPROM is defective.
Main unit RAM fault
 The control RAM is defective.
 The control ROM is defective.
Main unit ROM fault
CPU fault 1
 The control CPU is defective.
Communication error
 The communication with external devices
is broken off.
Current detector fault
 The current detector is defective.
Optional unit fault 1
 An optional unit has failed.
(such as a communication option)
Remote keypad
 After run signal is activated by RUN key
disconnection fault
of the remote keypad, disconnection is
occurred in 10 seconds or more.
Description
M-3
E6582175
Remedies
 Enable  (over-torque trip selection).
 Check system error.
 Reduce the load.
 Increase the stall prevention level or
power running torque limit level.
 Enable .
 Reduce the load.
 Check system error.
 Enable .
 Check system error.
 The fan requires replacement if it does
not rotate during operation.
Contact your Toshiba distributor.
 Operate at a specified ambient
temperature
 Secure sufficient space around the inverter.
 Do not place any heat generating device
near the inverter.
 Reduce the load.
 Reduce f300 : PWM carrier frequency.
 Set f136= 1 (Carrier frequency with
automatic reduction)
 Contact your Toshiba distributor.
 The motor is overheated, so check
whether the current flowing into the motor
exceeds the rated current.
 Reset the inverter.
 If the emergency stop signal is input,
reset after releasing this signal.
 Turn off the inverter, then, turn it again.
If it does not recover from the error,
contact your Toshiba distributor.
 Turn off the inverter, then, turn it again,
and then try  operation again.
 Turn off the inverter, then, turn it again.
If it does not recover from the error,
contact your Toshiba distributor.
 Contact your Toshiba distributor.
 Contact your Toshiba distributor.
 Contact your Toshiba distributor.
 Contact your Toshiba distributor.
 Check the remote control device, cables,
etc.
 Contact your Toshiba distributor.
 Check the connection of optional unit.
 In case the remote keypad is
disconnected, press STOP key before.
 This fault is disabled by f731=1
setting.