Communication
:
option
:
Terminal VIC
:
Pulse train input
14:
sro
● The control input terminal in which the following functions are set is always valid regardless of the setting of
and .
Reset (valid only for tripping)
Standby
External input tripping stop command
Coast stop command terminal
● To make changes in the command mode selection and the frequency setting mode selection 1
, first stop the inverter temporarily.
(Can be changed while in operation when is set to .)
● Priority commands from communications or terminal blocks are given priority over .
Preset-speed operation
: Set to (Terminal block operation)
: Valid in all setting values.
Input terminal settings
Assign the following functions to the input terminal to allow switching of the frequency command by turning
the terminal ON/OFF.
Input terminal function
48
Forced local from communication
Frequency setting mode terminal
106
block
Each of the following numbers (49, 107) are reverse signals.
Frequencies are set by commands from a communication option.
Refer to each Instruction Manual of option.
A frequency command is set by means of external analog signals.
(VIC terminal: 0 (4) - 20mAdc)
Refer to section 3.2.2 and 7.3
A frequency command is set by means of external pulse train signals.
(S2 terminal: 10pps - 2kpps)
Refer to section 6.10.5
Frequencies are set by sro parameter.
Refer to section 5.7.
Enabled during communication
Local (Setting of , )
Terminal block (VIA) enabled
F-15
ON
Communication
setting of
E6582175
6
OFF