Note
Only those messages which are listed in the indexed parameters can be changed
as desired. All other message settings retain their factory settings or are reset to
the factory settings.
Examples:
S
In the case of messages listed via p2128[0...19], the message type can be
changed. The factory setting is set for all other messages.
S
The fault response of fault F12345 has been changed via p2100[n]. The factory
settings are to be reinstated.
--> p2100[n] = 0
Triggering on messages (example)
Select message
p2128[0] = 1001
or
p2128[1] = 1002
Note
The value for CO: r2129 can be used as a group trigger
CO: r2129 = 0 None of the selected message occurred.
CO: r2129 > 0 Group trigger.
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Trigger signal
BO: r2129.0
BO: r2129.1
At least 1 of the selected messages occurred.
The individual binector outputs BO: r2129 must be examined.
Diagnosis
Messages – faults and alarms
6-223