Siemens SINAMICS S120 Installation And Start-Up Manual page 251

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Example of replacing a component with a different order number
Prerequisite:
S The replaced component has a different order number
Table 7-11
S
Switch off the power
supply
S
Replace the defective
component and connect
the new one
S
Switch on the power
supply
S
Load the project from the
Control Unit to the
STARTER (PG)
S
Configure the
replacement drive and
select the current
component
S
Load the project to the
Control Unit (target
system)
The component has been successfully replaced
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Example of replacing a component with a different order number
Action
Alarm F1420
S
Alarm disappears
Basic Information about the Drive System
Response
The new order number is
stored in the RAM of the
Control Unit and has to be
copied to the non-volatile
memory with p0971 or
p0977.
DRIVE-CLiQ topology
Comments
7-251