27.11 Air-fuel ratio curves – settings and commissioning
P

27.11.1 Initial commissioning

P
For initial commissioning, change to the parameter level (refer to chapter Operation).
The settings can then be made on parameter level 400.
P
/reset
P
/reset
182/235
Building Technologies Division
Industry Sector
V
h min s
%
V
h min s
%
V
h min s
%
V
h min s
%
Basic documentation LMV37.4...
27 Parameter level
The display shows 400: flashing on the left,
SEt appears on the right.
An unprogrammed unit or a unit whose operating mode
has been reset or changed displays OFF UPr.
Press
to select parameter 400 for initial
/reset
commissioning and for setting air-fuel ratio control.
Press
to go to the settings for air-fuel ratio control
/reset
and parameter 201 for selecting the
operating mode.
201: appears flashing.
CC1P7546en
20.09.2013