Siemens SINAMICS S120 Installation And Start-Up Manual page 156

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

SINAMICS Safety Integrated (Booksize)
Safe standstill (SH)
Note
The grouping must be identical in both monitoring channels.
If a fault in a drive results in a "Safe standstill (SH)", this does not automatically
mean that the other drives in the same group also switch to "Safe standstill (SH)".
The assignment is checked during the test for the shutdown paths, whereby the
operator selects "Safe standstill" for each group. The check is drive specific.
Example: terminal grouping for "Safe standstill (SH)"
It must be possible to select/deselect "Safe standstill" separately for group 1
(drive 1 and 2) and group 2 (drive 3 and 4).
In addition, the same grouping for "Safe standstill" must be assigned on both the
Control Unit and the Motor Modules.
Select/
deselect
Select/deselect
SH
Group 2
Group 1
safety_sh_gruppe.vsd
Fig. 5-2
Example: terminal grouping for "Safe standstill (SH)"
5-156
Control Unit
SH
p9620
DI 6
X132.3
r0722.6
p9620
M
p9620
DI 7
X132.4
r0722.7
p9620
M
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
M
EP
Drive 1
Drive 2
Line
Single
Motor
Module
Module
Drive 3
Drive 4
Drive
1
Group 1
E Siemens AG, 2004. All rights reserved
M
M
M
EP
EP
EP
Double
Single
Motor
Motor
Module
Module
Drive
Drive
4
2
3
Group 2