Preparations for Commissioning
Rules for wiring with DRIVE-CLiQ
Drive line-up comprising four Motor Modules (chassis) with different pulse frequencies
Motor Modules with different pulse frequencies must be connected to different
DRIVE-CLiQ interfaces on the Control Unit.
In the following diagram, two Motor Modules (400 V; output v 250 kW; pulse fre-
quency 2 kHz) are connected to interface X101 and two Motor Modules (400 V;
output > 250 kW; pulse frequency 1.25 kHz) are connected to interface X102.
Note
This topology does not match the topology created offline by STARTER and must
be changed (see Subsection 2.3.4.)
Infeed 1
CU
Active
320
Line
Module
X103
X102
X402
X101
X401
X100
X400
Active
Interface
Module
X500
VSM
Fig. 2-5
Drive line-up (chassis) with different pulse frequencies
2-38
Drive 1
Drive 2
Single
Single
Motor
Motor
Motor
Module
Module
X402
X402
X401
X401
X400
X400
X500
X500
X520
X520
SMC
SMC
30
30
M
M
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Drive 3
Drive 4
Single
Single
Motor
Motor
Module
Module
X402
X402
X401
X401
X400
X400
X500
X500
X520
X520
SMC
SMC
30
30
M
M
E Siemens AG, 2004. All rights reserved
DRIVE–CLiQ
Encoder