Siemens SINAMICS S120 Installation And Start-Up Manual page 111

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 4-12
Description of A_STW1 (status word for B_INF), continued
Bit
Meaning
9
Control requested
10
Reserved
11
Bypass energized
12
12
Line contactor energized
Line contactor energized
13
14
Reserved
15
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Comments
Control requested
The programmable logic controller is
1
requested to assume control. Condition for
applications with isochronous mode: drive
synchronized with PLC system.
Local operation
0
Control only possible on device
-
-
Bypass energized
Pre-charging is complete and the bypass
1
relay for the pre-charging resistors is
energized.
Bypass not energized
0
Pre-charging not yet complete
1
Line contactor energized
0
Line contactor not energized
-
-
Communication via PROFIBUS
Cyclic communication
BICO
BO: r0899.9
-
BO: r0899.11
BO: r0899.12
BO: r0899 12
-
4-111