Siemens SINAMICS S120 Installation And Start-Up Manual page 109

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 4-10
Description of MSGW (message word), continued
Bit
Meaning
14
14
Reserved
Reserved
15
A_STW1 (status word for A_INF)
See function diagram [8926].
Table 4-11
Description of A_STW1 (status word for A_INF)
Bit
Meaning
0
0
Ready to power up
Ready to power up
1
1
Ready
Ready
2
2
Operation enabled
Operation enabled
3
3
Fault active
Fault active
4
4
No OFF2 active
No OFF2 active
5
Reserved
6
6
Power up inhibit
Power-up inhibit
7
7
Warning active
Warning active
8
Reserved
9
Control requested
10
Reserved
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Comments
1
0
Comments
1
Ready to power up
0
Not ready to power up
Ready
1
DC link pre-charged, pulses inhibited
0
Not ready
Operation enabled
1
Vdc = Vdc_setp
0
Operation inhibited
1
Fault active
0
No fault
1
No OFF2 active
0
OFF2 active
-
-
Power-up inhibit
1
Fault active
0
No power-up inhibit
1
Warning active
0
No alarm
-
-
Control requested
The programmable logic controller is
1
requested to assume control. Condition for
applications with isochronous mode: drive
synchronized with PLC system.
Local operation
0
Control only possible on device
-
-
Communication via PROFIBUS
Cyclic communication
BICO
BO: r0899.0
BO: r0899 0
BO: r0899.1
BO: r0899.1
BO: r0899.2
BO: r0899.2
BO: r2139.3
BO: r2139 3
BO: r0899 4
BO: r0899.4
-
BO: r0899.6
BO: r0899.6
BO: r2139.7
BO: r2139 7
-
BO: r0899.9
-
BICO
4-109