Siemens SINAMICS S120 Installation And Start-Up Manual page 127

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Error values in DPV1 parameter responses
Table 4-17
Error values in DPV1 parameter responses
Error
Meaning
value
0x00
Illegal parameter number
0x01
Parameter value cannot be
changed
0x02
Lower or upper value limit
exceeded
0x03
Invalid subindex
0x04
No array
0x05
Wrong data type
0x06
Illegal set operation (only reset
allowed)
0x07
Description element cannot be
changed
0x09
No description data
0x0B
No operating priority
0x0F
No text array exists
0x11
Request cannot be executed due
to operating status
0x14
Illegal value
0x15
Response too long
0x16
Illegal parameter address
0x17
Illegal format
0x18
No. of values inconsistent
0x19
Drive object does not exist
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Communication via PROFIBUS
Comments
Access to a parameter which does not exist.
Modification access to a parameter value
which cannot be changed.
Modification access with value outside value
limits.
Access to a subindex which does not exist.
Access with subindex to an unindexed
parameter.
Modification access with a value which does
not match the data type of the parameter.
Modification access with a value not equal to
0 in a case where this is not allowed.
Modification access to a description element
which cannot be changed.
Access to a description which does not exist
(the parameter value exists).
Modification access with no operating priority.
Access to a text array which does not exist
(the parameter value exists).
Access is not possible temporarily for
unspecified reasons.
Modification access with a value which is
within the limits but which is illegal for other
permanent reasons (parameter with defined
individual values).
The length of the present response exceeds
the maximum transfer length.
Illegal or unsupported value for attribute,
number of elements, parameter number,
subindex or a combination of these.
Write request: illegal or unsupported parameter
data format.
Write request: a mismatch exists between the
number of values in the parameter data and
the number of elements in the parameter
address.
You have attempted to access a drive object
that does not exist.
Acyclic communication
Add.
informa-
tion
-
Subindex
Subindex
Subindex
-
-
Subindex
Subindex
-
-
-
-
Subindex
-
-
-
-
-
4-127

Hide quick links:

Advertisement

Table of Contents
loading